  • Nominal sizes: 6.5, 7.5, 10, 12.5, and 20 Tons
  • Up to 11.2 EER / 14.8 IEER
  • For use with matching RHCLA models
Unit of Measure
Items
RACL

RACL Series

RACL

RACL Series

RACL

RACL Series

RACL

RACL Series

RACL

RACL Series
Voltage N/A 208 V230 V N/A 460 V N/A 208 V230 V N/A 460 V N/A 208 V230 V
Frequency N/A 60 Hz
Number of Phases N/A 3
Nominal Capacity N/A 6.5 TR N/A 6.5 TR N/A 7.5 TR N/A 7.5 TR N/A 10 TR
Number of Compressors N/A 1
Compressor - Rated Load Amperes (RLA) N/A 28.5 A N/A 12 A N/A 28.5 A N/A 12 A N/A 34.8 A
Compressor - Locked Rotor Amperes (LRA) N/A 164 A N/A 94 A N/A 164 A N/A 94 A N/A 240 A
Number of Fans N/A 1 N/A 1 N/A 1 N/A 1 N/A 2
Fan Motor - Full Load Amperes N/A 4 A N/A 2.5 A N/A 4 A N/A 2.5 A N/A 7.8 A
Minimum Circuit Ampacity N/A 38 A N/A 18 A N/A 38 A N/A 18 A N/A 49 A
Fuse or HACR Circuit Breaker - Minimum N/A 45 A N/A 25 A N/A 45 A N/A 25 A N/A 60 A
Fuse or HACR Circuit Breaker - Maximum N/A 60 A N/A 25 A N/A 60 A N/A 25 A N/A 80 A
Outdoor Coil - Face Area N/A 32.44 ft² N/A 32.44 ft² N/A 32.44 ft² N/A 32.44 ft² N/A 32.88 ft²
Outdoor Coil - No. Rows N/A 2
Outdoor Coil - CFM N/A 5700 ft³/min N/A 5700 ft³/min N/A 5700 ft³/min N/A 5700 ft³/min N/A 8000 ft³/min
Refrigeration Per Circuit N/A 344 oz N/A 344 oz N/A 344 oz N/A 344 oz N/A 422 oz
Depth N/A 35.75 in N/A 35.75 in N/A 35.75 in N/A 35.75 in N/A 38.375 in
Width N/A 35.75 in N/A 35.75 in N/A 35.73 in N/A 35.73 in N/A 73 7/8 in
Height N/A 51 in N/A 51 in N/A 51 in N/A 51 in N/A 44.75 in
Weight N/A 375 lb N/A 375 lb N/A 375 lb N/A 375 lb N/A 565 lb
Features N/A
  • CABINET—All access panels can be opened or removed without affecting the structural strength of the unit. Stamped louvered panels offer 100% protection for the condenser coil.
  • EQUIPMENT GROUND—Lug for field connection of ground wire.
  • CONTACTOR—The contactor is an electrical switch which operates the compressor and outdoor fans. Its 24 volt coil is
  • activated on a call for cooling or heating.
  • TRANSFORMER—75 VA step-down type, from Line to 24 volts with resetable circuit breaker.
  • AUTO-RESET HIGH PRESSURE CONTROL, AND AUTO-RESET LOW PRESSURE CONTROL—To provide compressor protection under abnormally high head pressure conditions (outdoor fan failure, restriction, dirty coil, etc.) or abnormally low suction pressure conditions (restrictions, TEV failure, loss of charge, indoor blower failure, etc.) while eliminating nuisance tripping sometimes experienced with conventional control systems.
  • COIL—Constructed with copper tubes and aluminum fins mechanically bonded to tubes for maximum heat transfer capabilities. All coil assemblies are leak tested up to 550 PSIG (3792 kPa) internal pressure.
  • SERVICE ACCESS—Control box with separate line and control voltages, as well as compressor and other refrigerant controls are accessible through access panels. An electrical access cover may be opened or removed without affecting normal operation of the unit. Condenser fan motors are equipped with molded plugs for easy removal. Louver panels and end access panel can be removed for coil cleaning.
  • BASE PAN—Galvanized steel with weather-resistant baked enamel finish.
  • COMPRESSOR—The Scroll Compressor is hermetically sealed with internal high temperature protection, and durable insulation on motor windings. The entire compressor is mounted on rubber grommets to reduce vibration and noise.
  • SUCTION LINE ACCUMULATOR—To prevent liquid slugging of compressor.
  • REFRIGERANT CONNECTIONS—All field sweat joints are made external of the unit and are located close to the ground for a neat looking installation
  • SERVICE VALVES—Standard on liquid line and vapor line.